When a data center adds large lithium-ion battery banks, the fire-safety terms that carry the force of law come from the fire code its state or city has adopted, applied project by project by a local fire code official. The insurer writing the property policy often asks for more on spacing, sprinklers and siting, but those terms bind the owner as conditions of coverage, not as permit requirements.
The distance between the two can be wide. Washington State's adopted fire code requires lithium-ion systems to be split into groups of no more than 50 kilowatt-hours (kWh, a measure of stored energy) set at least three feet apart, and lets the fire code official approve tighter spacing based on fire testing. Tyler Ahrenhold, who heads the construction and inland marine division at commercial insurer MSIG USA, told Facilities Dive in September 2026 that his company's minimum spacing between a battery or on-site power source and a nearby building is 100 feet. The two figures measure different gaps (between battery groups in one case, between batteries and a building in the other), but they show how far an insurer's expectations can sit from the code minimum.
The question is coming up more often. Facilities Dive reported that states and municipalities are making bring-your-own-power a condition of data center approval, and Ahrenhold said sites with on-site turbines or batteries face roughly ten times the fire or explosion risk of grid-only sites. Allianz Commercial, in a 2026 report on data center risks, said lithium-ion batteries are increasingly used in or near server rooms, where a failure can set off thermal runaway, a self-sustaining, high-temperature fire inside battery cells that is difficult to control.
The binding layer: an adopted code and a fire official
Two model documents shape most battery fire rules: Section 1207 of the International Fire Code and NFPA 855, the National Fire Protection Association's Standard for the Installation of Stationary Energy Storage Systems. A model code becomes law only when a government adopts it. Washington, for example, adopted its version of Section 1207 as a state building code rule, WAC 51-54A-1207, filed in October 2023 and effective March 15, 2024.
Under that rule, lithium-ion systems larger than 20 kWh fall under the section. It sets a maximum allowable quantity of 600 kWh for lithium-ion storage, a cap that, where the code allows, can be raised on the basis of a hazard mitigation analysis. The exceptions in the text written for uninterruptible power supplies (UPS, the battery systems that carry servers through an outage until generators start) cover lead-acid batteries, so a lithium-ion UPS bank does not get that relief under the text.
Much of the practical decision rests with the fire code official. The Washington rule requires a hazard mitigation analysis, a structured study of what happens when a single component fails, such as one battery unit going into thermal runaway, in several situations, including whenever the official requires one for a hazard the code does not otherwise address. Where large-scale fire testing is required, it must follow UL 9540A, a test method that shows whether a fire in one battery unit spreads to its neighbors, and the report goes to the official for review and approval. The official may approve larger capacities or smaller separation distances on the basis of that testing, and may require trained personnel to be dispatched to a damaged system if public safety calls for it.
The standards themselves are moving. Engineering firm Exponent wrote in March 2026 that the 2026 edition of NFPA 855 makes a hazard mitigation analysis the default for most battery installations, requires explosion control under NFPA 69 or a performance-based alternative backed by testing, and no longer accepts deflagration venting (panels that release the pressure of a fast-burning gas explosion) as the primary explosion strategy. Exponent expected the changes to affect how permitting authorities review projects. Those requirements apply only where a jurisdiction adopts that edition; the Digest could not open a current national adoption table, so the edition in force near any given site has to be checked in that state's or city's code. Fire protection contractor ORR Protection said in 2023 that data center battery rooms fall under NFPA 855's provisions for buildings with other uses, and that the edition enforced locally can lag the latest one.
For residents, the binding documents are public in principle. The Washington rule lists what an owner must submit to the fire code official, including a commissioning plan, a decommissioning plan and a fire safety and evacuation plan. The same rule says plans for utility-owned storage that North American Electric Reliability Corporation rules and other laws treat as critical infrastructure documents are made available to the fire official for viewing under those rules rather than simply filed.
California adds a state process
California shows how a state can layer process on top of the code. A Senate floor analysis of Senate Bill 283 reported the authors' statement that the California Fire Code published July 1, 2025, and effective January 1, 2026, includes NFPA 855. ESS News reported that the Office of the State Fire Marshal adopted the standard in March 2025, which is why a requirement to comply with NFPA 855 was dropped from the bill.
SB 283 (Laird), the Clean Energy Safety Act of 2025, passed the Senate 38-0 and the Assembly 80-0 and was signed by Gov. Gavin Newsom, with an effective date of January 1, 2026, according to ESS News. It requires an applicant to certify that it met with the local fire authority at least 30 days before filing, and bars approval unless the fire authority inspects the system after installation and before operation, at the applicant's cost. The analysis says the bill applies to charter cities as a matter of statewide concern.
The law covers storage systems of 10 megawatt-hours (10,000 kWh) or more, a threshold the analysis described as largely intended to capture utility-scale facilities. Whether a given data center's backup or grid-support bank crosses it depends on the design; the sources reviewed here do not say how many California data center systems do. The bill also directs the State Fire Marshal, in the next building code update considered after July 1, 2026, to review and consider proposing rules that would restrict such systems to dedicated noncombustible buildings or outdoor sites, an option that would bear directly on indoor battery rooms.
The insurer's rulebook
Insurers apply their own engineering standards. FM Global's Property Loss Prevention Data Sheet 5-33, which FM describes as loss prevention recommendations, covers stationary lithium-ion systems above 20 kWh. The Digest read the January 2024 interim revision, the latest version it could open; FM may have revised it since. It ranks locations in order of preference, starting with an outdoor enclosure away from critical buildings, then a dedicated battery building, then cutoff rooms (fire-rated rooms separated from the rest of the building) with exterior walls.
Its distances are generally larger than the Washington rule's three feet. For outdoor containers, it recommends aisles of at least 5 feet, on sides with doors, access panels or vents, for lithium iron phosphate (LFP) cells and 13 feet for nickel manganese cobalt (NMC) cells, two common lithium-ion chemistries, or 8 feet for NMC containers with one-hour rated walls. Indoors, it recommends 6 feet from a rack's accessible face to other racks and noncombustible materials and 9 feet to combustibles, two-hour fire-rated rooms, construction designed to relieve explosion pressure, and sprinklers delivering 0.3 gallons per minute per square foot over the whole room plus 250 gallons per minute for hoses, with water for 45 minutes per adjacent rack. It also says not to use refurbished cells or modules.
The data sheet expressly excludes lithium-ion backup units installed in the server racks of data halls. FM publishes a separate data sheet for data centers, 5-32, which the Digest could not open. Allianz's report said lithium-ion batteries, unlike lead-acid units kept in separate battery rooms, are increasingly built directly into server racks.
Insurers enforce these preferences through how much risk they take, not through permits. Ahrenhold said insurers lean on best practices more than codes, that there is no regulatory code insurers can rely on to prevent a bad outcome from inadequate spacing or a poor site plan, and that his company can take a smaller share of a project's coverage or decline it if it doubts the design or team. Because large campuses are insured by several companies, he said, each insurer decides how large a share to take. Allianz said fire is the leading driver of loss severity in its data center claims and warned that suppression systems can themselves damage equipment through accidental discharge or contamination. The Digest found no public record setting out a specific insurer's battery conditions for a named US data center.
What the failure record shows
What to watch
California's State Fire Marshal is directed to consider restricting large storage systems to dedicated noncombustible buildings or outdoor sites in the next building code update considered after July 1, 2026; the materials reviewed here do not show whether a proposal has been made. SB 283's pre-application meeting and pre-operation inspection rules have applied since January 1, 2026, so the first California projects of 10 MWh or more approved under them will show how fire authorities use that leverage.
Adoption of the 2026 edition of NFPA 855 by states and cities has no date in these sources; readers can check the edition cited in their own fire code. On the insurance side, Ahrenhold said policies typically renew once a year, and JLL, cited by Facilities Dive, expects about 100 gigawatts of new US data center capacity to come online by 2030, which will put more battery banks in front of both fire officials and underwriters.
States in this story
- Facilities Dive — “On-site power, storage raise data center fire risk tenfold, insurer says”
- Washington State Legislature — “WAC 51-54A-1207 Electrical energy storage systems”
- Exponent — “NFPA 855 Expands Safety Guidelines for Battery Energy Storage Systems”
- FM Global (copy hosted by fireprotectionsupport.nl) — “Property Loss Prevention Data Sheet 5-33, Lithium-Ion Battery Energy Storage Systems (Interim Revision January 2024)”
- California Senate Rules Committee, Office of Senate Floor Analyses — “SB 283 (Laird) Senate Floor Analysis, Unfinished Business”
- ESS News — “California adopts battery storage safety legislation following Moss Landing fire”
- EPRI Storage Wiki — “Storage Safety”
- Allianz Commercial — “Data Centers: Risks and Claims Trends”
- ORR Protection — “Lithium-Ion Battery Q&A Series: Data Center Code Compliance”